Typical AGM Charge and Float Voltages at Various Temperature Ranges
| Temp. ˚F | Charge | Float | Temp. ˚C | ||
|---|---|---|---|---|---|
| Standard | Maximum | Standard | Maximum | ||
| > 120 | 13.60 | 13.90 | 12.80 | 13.00 | > 49 |
| 110-120 | 13.80 | 14.10 | 12.90 | 13.20 | 43-49 |
| 100-110 | 13.90 | 14.20 | 13.00 | 13.30 | 38-43 |
| 90-100 | 14.00 | 14.30 | 13.10 | 13.40 | 32-38 |
| 80-90 | 14.10 | 14.40 | 13.20 | 13.50 | 27-32 |
| 70-80 | 14.30 | 14.60 | 13.40 | 13.70 | 21-27 |
| 60-70 | 14.45 | 14.75 | 13.55 | 13.85 | 16-21 |
| 50-60 | 14.60 | 14.90 | 13.70 | 14.00 | 10-16 |
| 40-50 | 14.80 | 15.10 | 13.90 | 14.20 | 4-10 |
| < 40 | 15.10 | 15.40 | 14.20 | 14.50 | < 4 |
| Discover™ AGM | |||||
| 77˚F | 14.20 | 14.72 | 13.40 | 13.80 | 25˚C |
.